Suspended EC Crossflow ERV
This ceiling-mounted energy recovery ventilator (ERV) uses a crossflow core and offers several cabinet and control configurations.
MountingCeiling mounted
Electrical120 V, 60 Hz
Specifications
| Size / configuration | Rated airflow at external static pressure | Dimensions (W × D × H) | Sensible recovery efficiency (SRE) |
|---|---|---|---|
| 61 CFM, standardListed in stock | 61 CFM at 0.4 in. w.g. | 22 × 21 × 10 in. | 73% at 42 CFM net supply, 32°F entering supply, 25 W |
| 61 CFM, recirculation | 61 CFM at 0.4 in. w.g. | Confirm with Engineering | — |
| 162 CFM, standard, compact cabinetListed in stock | 162 CFM at 0.4 in. w.g. | 27 × 24 × 10 in. | 71% at 49 CFM net supply, 32°F entering supply, 18 W |
| 162 CFM, recirculation, compact cabinet | 162 CFM at 0.4 in. w.g. | Confirm with Engineering | — |
| 162 CFM, standard, large cabinetListed in stock | 162 CFM at 0.4 in. w.g. | 32 × 25 × 10 in. | — |
| 162 CFM, recirculation, large cabinet | 162 CFM at 0.4 in. w.g. | Confirm with Engineering | — |
| 61 CFM — constant airflow — stock-list configuration | 61 CFM at 0.4 in. w.g. | Confirm with Engineering | — |
| 150 CFM — constant airflow — stock-list configuration | 150 CFM at 0.4 in. w.g. | Confirm with Engineering | — |
| 162 CFM — constant airflow — stock-list configuration | 162 CFM at 0.4 in. w.g. | Confirm with Engineering | — |
Stock list dated November 16, 2026.
Total recovery efficiency (TRE) 54.5% at 42 CFM net supply and 95°F entering supply, 25 W.
Listed dimensions include duct collars, controls and latches.